PRODUCTS » Flow Meters
  PADDLE WHEEL
 
FEATURES
 
Paddle wheel flow meters belong to the category of insertion type flow meters. The rotating paddle wheel generates a signal in proportion to the velocity of the moving fluid which is read in terms of the flaw rate. Because the pipe's cross-sectional area is known and remains fixed the average velocity is an indication of the flow rate.  
   
SPECIFICATIONS
 
Flow Range : 0.5m/sec to 5m/sec
Max. Op. Temperature : 70 deg c
Max. Op. Pressure : 10 kg/sq.cm
Power Supply : 230 V~AC/24V DC
Pressure Drop : <0.1 kg/sq.cm.
Line Size : 0.5" to 48"
     
MATERIAL OF CONSTRUCTION
 
Transducer Housing : POLYPROPYLENE
O-rings : NEOPRENE
Shaft : SS316/HASTALLOY C/PVDF
Rotor : NYLON/PVDF
Maximum %solids : 1% of fluid volume, non-abrasive, non-magnetic, <100 micron in diameter and length
Max. Viscosity : 1 Cp(water) upto 5Cp above 1.5m/sec
Output : 1line 16 chr. LCD display/1line LED/2line LED
Register : Rate of flow - m3/hr Total flow-m3
Standard Cable Length : 1.5mtrs power supply cable for field mounted versions and 10 mtrs signal transmission cable for panel mounted versions
Process Connection : PP wafer drilled as per BS10Table E/ANSI B16.5/SS stub/Glue-on PVC saddle
   
INSTALLATION FITTINGS
 
All installation fittings are supplied along with the flow sensor. The sensor may be installed in a PP wafer drilled asper BS10 TABLE E OR ANSI B16.5 standards or a Glue-on PVC saddle or a SS stub welded to a MS/SS plate.  
   
   
ADD-ON FEATURES *
   
   
RELAY OUTPUT
 
  • 230vac, 1a (Resistive load only) max. with 1NO and 1NC contact. 1 or 2 Relay outputs can be given for giving a signal based on flow rate or total flow or both depending upon the requirements.
  • Customer to clearly specify the number of relay outputs required and also whether the cut-off signal is to be based on rate of floe or total flow.
 
INTERFACING WITH PLC
 
An open collector pulse output or a 4-20mA signal can be provided for interfacing with a PLC or connecting to Recorders.  
   
   
DOSING APPLICATION
  Programmable pulsed output available
   
   
THE DOWNTIME ELIMINATOR WET TAP VALVE ASSEMBLY
 
You can completely eliminate downtime resulting from flow sensor maintenance, with the simple addition of the Wet Tap Valve assembly. Should a sensor, rotor, or O-ring need to be replaced, the wet tap assembly provides a safe and fast method of removing a specially extended sensor from your pipe without system shut-down.  
 
  THERMAL MASS FLOW METER / CONTROLLER
FEATURES
 
  • Accuracy: ±1% of full scale including linearity
  • Repeatability: ±0.15% full scale or better
  • Turndown Ratio: 100:1
  • Response Time: 1 second
  • Gas Ambient Temperature: 0 to 60°C
  • Temperature Coefficient: 0.05% full scale per 1°C or better
  • Pressure Coefficient: 0.01% full scale per PSI or better
  • Minimum Pressure Requirements: Meters: 1 inch of H2O
  • Maximum Gas Pressure: 500psi–SS316
  • Leak integrity: 1 x10-6 cc/min of He or better
  • Wetted Parts: 316 SS, Viton® O-rings
  • Connections: 3/4” NPT(F), standard
  • Input/Output Connection: 9-pin sub-D connector
  • Output signal: Linear 0-5 Vdc,1000 ohms min load, 4-20 mA, 500 ohms loop resistance
  • Input Power: Meters: 24 Vdc @ 300 mA, 115 Vac, 220 Vac with ac adaptor
  • Weight: 6.8 kg with power supply