PRODUCTS » Fuel Meters
|
 |
| |
DM100 & DM150
FLOW METER PLUS FILTER
|
|
 |
 |
| |
|
|
 |
| |
| The DM100 has been
designed to measure diesel, kerosene and petrol,
and is made from corrosion resistant aluminium with
easy to read mechanical register. |
 |
|
| |
|
|
 |
 |
FEATURES |
 |
- Oval gear design
- Low pressure drop allows for gravity and pump
(in-line) applications
- Register cap can be easily removed and rotated
to every 90° orientation for display reading
|
- Supplied with integrated mesh strainer
- 10 year warranty
- 10 year parts availability
|
|
 |
 |
SPECIFICATIONS |
 |
| |
| Wetted
Components: |
Aluminum,
Zinc plated Carbon Steel, PEI Resin, Viton |
| Accuracy: |
±
1% of reading |
| Flow range: |
3 - 80 L/min (0.8
- 21 US gal/min) |
| Max. Pressure: |
1000 kpa (145 psi,
10 bar) |
| Register –
Totaliser: |
0 – 999,999
L (gal) |
| Register –
Reset: |
0 – 999.9
L (gal) |
| Max. Temp: |
80° C (176°
F) |
| Inlet Thread: |
1” BSPT, 1”
BSPPL(G) or 1” NPT female |
| Outlet Thread: |
1” BSPT, 1”
BSPPL(G) or 1” NPT female |
| Weight: |
1.2 kg (2.6 lbs) |
|
| |
|
|
| |
 |
|
|
IM40/50/75 |
|
 |
 |
| |
|
| |
|
| |
| |
The
IM50 & 75 have been designed specifically to
dispense lubricating oils, diesel and kerosene.
These high pressure, positive displacement-type
meter are suitable for all in-line and end-of-line
applications and features a rugged and robust register
with integrated electronics and large LC display. |
 |
|
 |
| |
|
|
 |
 |
FEATURES |
 |
- Robust aluminium construction and fully sealed
against dust and water splash
- Easy to read and operate resetable six-digit
display with ability to show batch, reset total,
non-reset total and rate of flow
- User selectable display units: Litres, Gallons,
Pints, Quarts
- Available with LC display or pulse output
(pulse output model with 1 m fly lead available
with either reed switch or hall effect sensor)
- Average battery life of two years (battery
type: 2 x AAA alkaline)
- Protective boot standard on LCD version -
optional coloured boots available: red, blue,
yellow, green, black
- 10 year warranty
- 10 year parts availability
|
 |
|
 |
SPECIFICATIONS
- IM50/IM50P |
| Wetted
Components: |
Acetal
(suitable with oils), Aluminium, Nitrile (NBR),
mild steel |
| Accuracy: |
±0.5%
of reading |
| Flow range: |
1-30 L/min (0.26-8
US gal/min) |
| Max.Working Pressure: |
1 030 kPa (150 psi,
10.3 bar) |
| Inlet Thread: |
1/2” BSPT
or NPT (F) |
| Oulet Thread: |
1/2” BSPT
or NPT (F) |
| Operating Temperature: |
5ºC (41ºF)
to +55ºC (131ºF) |
| Weight (approx):
|
430 g (0.95 lbs) |
| K factor: |
112ppL (424 pp USG) |
|
| |
| |
 |
SPECIFICATIONS
- IM75/IM75P |
| Wetted
Components: |
PEI
Resin, Aluminium, Nitrile (NBR), Mild Steel Mild
Steel |
| Accuracy: |
±0.5%
of reading |
| Flow range: |
3-60 L/min (0.8-15.8
US gal/min) |
| Max.Working Pressure: |
10 350 kPa (1 500
psi, 103.5 bar) |
| Inlet Thread: |
3/4” NPT (F) |
| Oulet Thread: |
3/4” NPT (F) |
| Operating Temperature: |
5ºC (41ºF)
to 800C (176ºF) for IM75P |
| Weight (approx): |
980 g (2.16 lbs) |
| K factor: |
54.6 ppL (206.5
pp USG) |
|
| |
|
|
| |
 |
|
|
TM100 |
|
 |
 |
| |
|
| |
|
 |
| |
| The
TM100W turbine flow meter has an excellent turndown
ratio and is factory calibrated for precise measurement
of low viscosity fluids. The low-pressure drop and
high pressure rating allows the turbine meter range
to be used in gravity, pump and inline applications. |
 |
|
| |
|
|
 |
 |
FEATURES |
 |
- Available in LCD (TM100W) and pulse (TM100WP) versions
- High accuracy (better than ± 3 % of reading)
- Excellent turndown ratio: 28:1
- Nylon construction and fully sealed against dust
and water splash
- Flow linearisation (display version)
- Field programmable
- Easy to read and operate resetable six-digit display
with ability to show batch, reset total, non-reset
total and rate of flow
- Average battery life 2 years (2 x AAA alkaline)
- Protective boot standard on LCD version –
optional coloured boots available: red, blue, yellow,
black and green
- 10 year warranty
- 10 year spare parts
|
 |
 |
SPECIFICATIONS |
 |
| Port Size: |
1” BSPT /
NPT, fully moulded |
| Wetted
Components: |
Nylon,
Tungsten, Ceramic |
| Maimum Pressure: |
1.030 kPa (150 psi,
10.3 bar) |
| Flow: |
10 to 200 L/min
(2.6 to 52.8 US gal/min) |
| Accuracy: |
Better
than ± 3 % of reading |
| Flow compatibility: |
Water, Low viscosity
fluids that do not attack Nylon |
| Max.Working Pressure: |
10 350 kPa (1 500
psi, 103.5 bar) |
| TM100W
LCD |
| Digits: |
12mm size and maximum
of 6 digit display |
| Decimals: |
Selectable 0 to
3 |
| Inlet Thread: |
3/4” NPT (F) |
| Totals: |
Batch / Reset Total
/ Non Reset Total / Rate |
| Temperature Range: |
00C to 550C (320F
to 1310F) |
| TM100WP
Pulse |
| Operating Voltage: |
12 to 30 V DC |
| Polarity Protection |
YES |
| Output: |
Open collector,
maximum 1Watt peak (unfactored) |
| Electrical Connection: |
PCB terminal strip16
mm or 1/2” NPT conduit |
| Operating Temperature: |
00C to 550C (320F
to 1310F) |
| Temperature Range:
|
00C to 550C (320F
to 1310F) |
| K factor: |
41.9 ppL (158.6
pp USG) nominal at 100L/min |
|
| |
|
|
|
 |